Skip to main content
VoltCalcs

Locked Rotor Amps (LRA) Calculator

Enter the motor nameplate code letter, horsepower and voltage to get its locked-rotor current band.

NEMA nameplates print the locked-rotor code letter in the CODE field. Pick the second mode if your nameplate or data sheet prints its own locked-rotor amps.

0.5–500 hp

100–600 V

The nameplate PH field: 3 or 1.

The letter in the nameplate CODE field (locked-rotor kVA per horsepower). Read in the code letter mode.

0–10000 A

0.1–1000 A

Enter values and click Calculate

Source: LRA = kVA per hp of the nameplate code letter (NEC Table 430-7(b), MSHA reprint of NFPA 70-1968) x hp x 1,000 / (1.732 x V) three-phase, or / V single-phase

8 min read
Calculate the starting inrush current (locked rotor amps) of a motor from its NEMA code letter or its printed LRA. This number determines your breaker size, starter rating, and whether your generator or inverter can handle the startup surge without tripping. Our motor FLA guide explains how LRA relates to breaker selection and overload protection.
Locked rotor amps 281.2 to 313.5 A for 10 HP at 230 V three-phase code N, 11.2 to 12.49 kVA/hp, ABB typical 6x FLA.

NEMA Code Letters: Locked-Rotor kVA per Horsepower

NEMA Code LetterkVA per Horsepower with Locked Rotor
A0 - 3.14
B3.15 - 3.54
C3.55 - 3.99
D4.0 - 4.49
E4.5 - 4.99
F5.0 - 5.59
G5.6 - 6.29
H6.3 - 7.09
J7.1 - 7.99
K8.0 - 8.99
L9.0 - 9.99
M10.0 - 11.19
N11.2 - 12.49
P12.5 - 13.99
R14.0 - 15.99
S16.0 - 17.99
T18.0 - 19.99
U20.0 - 22.39
V22.4 - and up

These rows are Table 430-7(b), "Locked Rotor Indicating Code Letters", as MSHA's reprint of the 1968 National Electrical Code (NFPA 70-1968) prints them; the letters I, O and Q are not used. For a three-phase motor the calculator works LRA = kVA/hp × hp × 1,000 ÷ (1.732 × V), with 1.732 as Land and Electric prints the square root of 3; for a single-phase motor it divides by V alone. ABB, a motor maker, and Rockwell Automation, a motor-control maker, print the same code letters, A to V, with bands that differ from this table's only in how an upper edge is written, and we have not opened NFPA's own text of Table 430.7(B), so confirm the letter's band against the NEC edition your jurisdiction has adopted or your authority having jurisdiction. Compressors and high-torque applications often land in the H-K range. Check the motor nameplate for the NEMA code letter.

Motor hpNEMA MG 1 Table 12-1B maximum at 230 VCode letter in that rowThat letter's band at 230 V, three-phase
131.3 AN28.1 to 31.4 A
5100 AJ89.1 to 100.3 A
10175 AH158.1 to 178 A
25394 AG351.4 to 394.7 A
1001578 AG1405.8 to 1579 A

NEMA MG 1 prints these maximum locked-rotor currents for Design B, C and D motors at 230 volts; each sits inside the band of its own code letter, and the maximum at another voltage is "inversely proportional to the voltages." ABB's Motor Protection Fundamentals webinar puts the starting current as "typically 6 times the Full Load Current"; this calculator returns the code letter band instead. Baldor's data sheet for its EM3581T motor (1 HP, code N) prints "Starting Current 14.4 A" at 460 V ("Typical performance; not guaranteed values."); the code N band for that motor at 460 V is 14.1 to 15.7 A.

NEMA code letters A, D, H, L and R against locked-rotor kVA per hp band top, edges as MSHA prints them.
Code letter band tops 3.14, 4.49, 7.09, 9.99 and 15.99 kVA per hp as MSHA prints them, codes A, D and H drawn to one decimal.

What Happens When a Motor Starts

When you apply power to a stopped motor, the rotor is not turning. The motor's windings see full voltage across zero back-EMF (the voltage a spinning rotor generates to oppose the supply). With no back-EMF, the windings behave almost like a short circuit, and current surges to several times the running amps. Our explainer on why motors spike at startup walks through the physics and the code-letter method in depth.

This inrush lasts 0.5-3 seconds for most motors. As the rotor accelerates, back-EMF builds and current drops toward normal FLA. A Baldor EM3581T (1 HP, code N, 3.26 A full load at 230 V three-phase) draws 28.1 to 31.4 A by its code letter band as it starts. That band is what your breaker, wiring, and power source must survive without tripping or sagging.

The locked rotor condition is the worst case: the rotor is physically prevented from turning (locked), so inrush current never subsides. A motor that jams (seized bearing, stuck compressor, frozen pump) draws locked rotor amps continuously until the overload relay opens or the breaker trips. This is why motor circuits use dual protection: a breaker sized for starting inrush (250-300% of FLA) and an overload relay sized for running current (115-125% of FLA).

Temperature affects starting current too. A cold motor has lower winding resistance and draws slightly more inrush than a warm one. If you are sizing protection for a motor in an unheated shop that starts from cold every morning, use the top of the code letter's band.

Example: Sizing a Starter for a 5HP Compressor

A 5HP three-phase air compressor at 230V has a nameplate FLA of 15.2A and a NEMA code letter of H. Code H prints 6.3 to 7.09 kVA per horsepower, so the LRA is 79.1 to 89 A.

To handle this startup surge, you need:

  • Breaker: 250% of 15.2A = 38A. Next standard size is 40A inverse-time breaker. NEC Article 430 allows up to 250% for inverse-time breakers because the brief 79.1 to 89 A inrush does not trip a thermal breaker fast enough to cause a nuisance trip.
  • Contactor: Rated for at least the FLA (15.2A) with an inrush rating matching the LRA. A NEMA Size 1 starter is rated 27A continuous with a published closing-inrush rating of 288A peak. That covers this motor with room to spare.
  • Overload relay: Set to 115% of FLA = 17.5A. This trips on sustained overcurrent but rides through the brief starting surge.
  • Wiring: Must carry 125% of FLA = 19A minimum. 12 AWG copper handles that, but check voltage drop if the run exceeds 50 feet.

If you do not know your motor's FLA, our motor FLA calculator reads the printed table's current by horsepower, voltage and phase, and its page gives the nameplate formula, from horsepower, voltage, efficiency and power factor, as a second figure to check against the nameplate.

Running this compressor off a battery-powered inverter? The inverter must handle the top of the band, 89 A. An inverter whose surge rating is 2x continuous surges to about 26A at 3,000W and 230V. You would need a much larger inverter or a soft starter to reduce the inrush. Our battery size for inverter calculator can help you figure out how much battery capacity the system needs.

Worked Examples

What a Code N Nameplate Means at 230 V

Context

Baldor's data sheet for its EM3581T motor prints 1 HP, three-phase, 230/460 V, 3.260 A full load at 230 V and KVA Code N. You want the current it draws as it starts on a 230 V supply.

Calculation

Code N: 11.2 to 12.49 kVA/hp × 1 hp × 1000 ÷ (1.732 × 230 V) = 28.1 to 31.4 A

Against the 3.26 A full-load current: 8.6× to 9.6×

Interpretation

NEMA MG 1 Table 12-1B prints 31.3 A as the maximum locked-rotor current of a 1 hp, code N motor at 230 volts, inside this band. For a moment the start draws 8.6 to 9.6 times the running current.

Takeaway

Size the generator or inverter for the start from the top of the band, 31.4 A, not from the 3.26 A running figure. To size a battery backup instead, use our UPS battery backup calculator and check that the inverter's surge rating covers the band.

Selecting a Motor Starter for a 100 HP Motor

Context

Baldor's data sheet for its EM4400T motor prints 100 HP, three-phase, 230/460 V, 112 A full load at 460 V and KVA Code G. It will run on 460 V. You need to size the magnetic contactor and overload relay.

Calculation

Code G: 5.6 to 6.29 kVA/hp × 100 hp × 1000 ÷ (1.732 × 460 V) = 702.9 to 789.5 A

Against the 112 A full-load current: 6.3× to 7×

Interpretation

The contactor must close on the starting surge without welding its contacts and then carry the running current. Choose a starter whose maker prints a continuous rating of at least 112 A and a closing-inrush rating above 789.5 A, the top of the code G band, and set the overload relay from the 112 A full-load amps by the relay maker's table.

Takeaway

The FLA used here comes from the motor nameplate. For the motor circuit, size the conductors and short-circuit protection from the full-load current of the printed motor table, not from the watts of our HP to watts calculator, and set the overload from the nameplate.

Frequently Asked Questions

Glossary

Locked Rotor Amps

The current a motor draws at the instant of startup when the rotor is stationary (locked). The nameplate code letter gives it as a band of kVA per horsepower, and it lasts 0.5-3 seconds depending on the load inertia.

NEMA Code Letter

A letter on the motor nameplate (A through V) indicating the locked rotor kVA per HP. Higher code letters mean higher starting current. Code A is the gentlest start; code V is the most aggressive.

Soft Starter

An electronic device that gradually ramps up voltage to the motor during startup, holding the inrush current below the across-the-line figure. Reduces mechanical stress, voltage dip, and breaker trips.

Planning to run motors from an off-grid battery system? Our battery runtime calculator shows if your bank has the energy capacity for the load.

Locked rotor amps is the number your breaker, generator, and inverter must survive during every startup. Underestimate it and you get nuisance trips. Ignore it and you risk a generator or inverter that cannot start the motor. For motors driving critical equipment, always verify the code letter or the printed LRA on the nameplate or data sheet and size protection accordingly. This page prints the band of locked-rotor current that the nameplate code letter gives for the horsepower, voltage and phase you enter; where the nameplate or data sheet prints its own locked-rotor amps, that figure governs. For critical installations, consult a licensed electrician.

More Electrical calculators

Browse all electrical calculators: Motor FLA, wire sizing, voltage drop, load calculations, and transformer fusing based on NEC standards.

Last updated:

Written and maintained by Dan Dadovic, Commercial Director at Ezoic Inc. & PhD Candidate in Information Sciences. On the energy side, Dan has hands-on experience with residential solar panel installation, DIY battery bank construction, off-grid power systems, wind power, and EV ownership/driving, all from building, maintaining, and operating his own systems.

Disclaimer: Calculator results are estimates based on theoretical formulas. Actual performance varies with temperature, battery age, load patterns, and equipment condition. For critical electrical work, consult a licensed electrician.

Methodology reviewed by Doc. dr. sc. Danijel Jerković-Štil, Assistant Professor, FERIT Osijek.