Skip to main content
VoltCalcs

Electrical Load Calculator

Dwelling service load by the optional method, line by line as the municipal worksheets print it.

0–20000 sq ft

2–20

1–10

0–50000 VA

1–100

0–50000 VA

1–100

0–50000 VA

1–100

0–50000 VA

1–100

Line 5: the first 10,000 VA of lines 1 to 4 at 100 percent and the rest at 40 percent (Sacramento, Rialto, Placer, Maricopa, Campbell). Campbell and Florence print 8,000 VA for an existing dwelling.

0–60000 VA

0–100000 VA

0–50000 VA

Sacramento and Rialto print the charger after the 40 percent line; Placer and Huntington Beach print it among the appliances, under the factor. Follow your own form.

Enter values and click Calculate

Source: NEC 220.82 optional method for a dwelling, as the worksheets of Huntington Beach, Sacramento, Rialto, Placer, Maricopa, Florence and Campbell print it

11 min read
This residential electrical load calculator runs the optional method for a dwelling line by line as the municipal worksheets print it. Floor area at 3 VA a square foot, the small-appliance and laundry circuits at 1,500 VA each and the appliances fastened in place at nameplate make the general load. The first 10,000 VA of it counts at 100 percent and the rest at 40 percent (8,000 VA for an existing dwelling, as Campbell and Florence print it). The larger of the air conditioning at 100 percent and the electric space heating at 65 percent is added after that factor, then the EV charger, and the total over 240 V is set against the next standard overcurrent rating, or against the 100 A minimum service three of the worksheets print where that rating is lower. The default is Placer County's printed sample house. Your own authority's worksheet governs: each input names the form that prints its line, and your building department's form may print a line this page does not. To turn a device's nameplate watts into amps first, our amps draw calculator works at any voltage.
Electrical load calculator banner at the page default: main panel service 150 A and home load 33,720 VA.

Load Figures the Worksheets Print

LineWhat the form printsForm
General lighting and receptacles3 VA per sq ftAll seven (Placer: "SF x 3 volt-amperes")
Electric rangeNameplate rating or 12,000Florence
Electric clothes dryerNameplate rating or 5,000; 5,000 watts (min)Florence; Sacramento and Rialto
Electric water heaterNameplate or 4,500Florence
Dishwasher, disposal, oven and other appliances fastened in placeNameplate ratingHuntington Beach, Placer, Sacramento, Rialto
Air conditioning100 percent of nameplate, after the factorPlacer, Sacramento, Rialto

The nameplate on the actual equipment is the number the worksheets ask for; Placer converts nameplate watts to volt-amperes at 1:1. To translate those nameplate watts into a monthly utility cost per appliance, our appliance electricity cost guide ranks the household energy hogs by annual spend.

Household electrical load table: water heater at nameplate or 4,500 W, dryer at nameplate or 5,000 W, the rest at nameplate.
On Sacramento's worksheet the range is taken at its nameplate rating in the general load, and the larger of 100% of the air conditioner and 65% of the heater is added after the 40% line.

Two NEC Ways to Size a Dwelling

The National Electrical Code gives you two legitimate ways to size a dwelling service, and they routinely land on different numbers. The standard method (Article 220, Part III) factors each load category on its own. The optional method (NEC 220.82) is the shortcut this calculator uses. Here is how each one treats the same dwelling loads.

LoadStandard method (Art. 220, Part III)Optional method (220.82)
Who can use itAny dwelling, feeder, or serviceDwelling on a single 100 A or larger, 3-wire 120/240 V service
General lighting3 VA/sq ft, then Table 220.45 (100% / 35% / 25%)3 VA/sq ft, added to the general-load total
Electric rangeA demand value from Table 220.55, or the nameplate where your own form asks for itFull nameplate, added to the general-load total
Other fixed appliances75% for four or more (220.53)Full nameplate, added to the general-load total
General-load factorapplied per category abovefirst 10 kVA at 100%, remainder at 40% (220.82(B))
Heating vs A/Clarger of the two only (220.60)largest of the 220.82(C) options
Stepsone factor per load categoryone factor on the general load

Neither method is "more correct." On the all-electric house of the first worked example below, the optional method gives the smaller service, and it takes fewer steps. The standard method is what you fall back on when a dwelling sits outside the 220.82 eligibility window, such as a service below 100 A. For a permit, your local jurisdiction decides which calculation it wants to see.

The Standard Method, Step by Step

The standard method walks each load category through its own demand factor. Here is the dwelling sequence, with the 2023 section numbers and the 2020 numbers where Article 220 was renumbered.

  1. Add the general lighting and receptacle load. Multiply the living area by 3 VA per sq ft (NEC 220.41, Table 220.12 in 2020), then add 1,500 VA for each small-appliance and laundry circuit (220.52).
  2. Apply the lighting demand factor. Table 220.45 (Table 220.42 in 2020) takes the first 3,000 VA at 100%, the portion from 3,001 to 120,000 VA at 35%, and anything above 120,000 VA at 25%.
  3. Size the electric range. Take the range at the demand value of Table 220.55, or at its nameplate where your own form asks for it. The optional-method worksheets on this page take it at nameplate (Sacramento: "Range (NPR - nameplate rating)").
  4. Apply the fixed-appliance demand factor. Four or more fastened-in-place appliances (water heater, dishwasher, disposal, and the like, but not the range, dryer, heat, or A/C) get a 75% factor under 220.53.
  5. Count heating or cooling, not both. Heating and A/C rarely run together, so 220.60 lets you drop the smaller of the two. Fixed electric heat is counted at the factor the code's standard method sets for it; the larger figure is the one you keep.
  6. Total and convert. Add the demand-adjusted categories, divide by 240 V for amps, and round up to the next standard service size.

Cited to NEC Table 220.45 and Table 220.55. The code text itself is not freely available to link; confirm the figure against the current edition or your authority having jurisdiction before acting.

This calculator does not run those category steps. It runs the optional method as the worksheets print it: the factor of 10,000 VA at 100 percent and the rest at 40 percent applies to lines 1 to 4 only, and Huntington Beach's form says of its appliance box, "Do not include any heating or air-conditioning equipment in this section." The heating and air-conditioning line and the EV charger line are added after the factor. For a permit, your own authority's worksheet governs.

What Size Service Do I Need?

Once you have a demand figure, the service size is mostly arithmetic: divide demand by 240 V and round up to the next standard rating. The table below is engineering guidance from that arithmetic plus the standard ratings in NEC 240.6(A), not a code table you read a required size straight out of. A one-family dwelling can never go below 100 A (NEC 230.79(C)). This calculator holds its result to that floor as three of the municipal worksheets print it: Huntington Beach (capture sha256 1464749897d7) prints "9. Minimum Size Service or Feeder 240.6(A) ... (minimum is 100 amperes)", and the Sacramento (capture sha256 a8d74f62155d) and Rialto (capture sha256 eacba9822122) worksheets print "2025 CEC 220.82 (100 AMP Minimum)". Where the next standard overcurrent rating is under 100 A, the result shows 100 A and names those three forms. On 1,000 sq ft with the two small-appliance circuits and one laundry circuit the forms print as minimums and nothing else, the load is 7,500 VA and 31 A; the next standard overcurrent rating is 35 A, so the result shows 100 A. Florence's existing-dwelling worksheet (capture sha256 86048b21dc2d) prints "service entrance or feeder conductors with an ampacity of 100 or greater" as the scope of its method, not as a minimum rating, and the Placer, Maricopa and Campbell worksheets print no minimum.

Service sizeMax load at 240 V
100 A24 kVA
125 A30 kVA
150 A36 kVA
200 A48 kVA
400 A96 kVA

Leave headroom. A panel running near its calculated limit has no room for the next upgrade, and an electric vehicle charger or heat pump can erase a comfortable margin fast. If you are planning battery backup for these loads during an outage, the UPS battery backup calculator shows how long a bank would carry the demand.

Worked Examples

Same House, Two Methods: Standard vs Optional

Context

A 2,400 sq ft all-electric dwelling has these loads: general lighting 7,200 VA (2,400 x 3 VA/sq ft), two small-appliance circuits and one laundry circuit at 1,500 VA each (4,500 VA), a 12 kW range, a 5,000 VA dryer, a 4,500 VA water heater, a 1,500 VA dishwasher, a 900 VA disposal, a 1,500 VA microwave, 5,000 VA of central A/C, and 10,000 VA of electric heat. What service does it need?

Calculation

Standard method (Article 220, Part III), the page's own arithmetic, outside the tool:

Lighting + small-appliance + laundry = 7,200 + 3,000 + 1,500 = 11,700 VA. Apply Table 220.45: first 3,000 at 100% (3,000) + remaining 8,700 at 35% (3,045) = 6,045 VA.

Range: 8,000 VA, the Table 220.55 demand value this hand calculation takes for the 12 kW range (the optional method below takes it at its 12,000 VA nameplate, as Sacramento's form prints "Range (NPR - nameplate rating)"). Dryer: 5,000 VA at 100%. Four fixed appliances (water heater, dishwasher, disposal, microwave) = 8,400 VA x 75% = 6,300 VA (220.53). Heat 10,000 VA beats A/C 5,000 VA, so keep 10,000 VA only (220.60).

Total = 6,045 + 8,000 + 5,000 + 6,300 + 10,000 = 35,345 VA. At 240 V that is 147 A, so a 150 A service.

Optional method, as the tool runs it (the fourth preset):

General load = floor area 7,200 + circuits 4,500 + range 12,000 + dryer 5,000 + water heater 4,500 + one appliance group of 3,900 (dishwasher 1,500, disposal 900, microwave 1,500) = 37,100 VA. The factor: first 10,000 at 100% (10,000) + remaining 27,100 at 40% (10,840) = 20,840 VA. After the factor, the larger of heat 10,000 x 65% (6,500) and A/C 5,000 x 100% (5,000) is 6,500 VA. Total = 20,840 + 6,500 = 27,340 VA. At 240 V that is 114 A; the next standard overcurrent rating is 125 A.

Interpretation

Same house, two answers: 150 A by the standard method worked by hand above, and 125 A by the optional method the tool runs. The optional method comes out lower here because the range and appliances go into one general load under one factor, and only the larger of the heating and the air conditioning is added after it.

Takeaway

Pick the method your jurisdiction accepts, then size the service above the result. Once the service size is set, the feeder or service-entrance conductors have to carry it over the run length; our wire distance calculator sizes the cable so voltage drop stays in spec.

Adding an EV Charger: Where the Worksheets Put It

Context

Placer County's printed sample is a 2,800 sq ft home with a 12 kW range, a 3 kW water heater, a 5 kW clothes dryer, a 1.5 kW dishwasher, 6.96 kW of air conditioning and a 7,000 VA EV charger. The worksheets place the charger in two ways. What does each give?

Calculation

Charger in the appliance lines, as Placer prints it: general load 8,400 + 4,500 + 12,000 + 3,000 + 5,000 + 1,500 + 7,000 = 41,400 VA; 10,000 + 31,400 x 0.40 = 22,560 VA; plus the air conditioning 6,960 VA = 29,520 VA; 29,520 / 240 = 123 A.

Charger on its own line after the factor, as Sacramento and Rialto print it: general load 34,400 VA; 10,000 + 24,400 x 0.40 = 19,760 VA; plus 6,960 VA and the charger's 7,000 VA = 33,720 VA; 33,720 / 240 = 140.5 A.

Interpretation

The same house and charger give 123 A on Placer's form and 141 A on Sacramento's. Against the next standard overcurrent rating, that is 125 A on the first and 150 A on the second. Your own authority's worksheet says which line the charger takes.

Takeaway

An EV charger is a continuous load (NEC 625.42), so its circuit is sized at 125% of the charger's rated current (625.41), and the 2023 code adds a dedicated EVSE load rule at 220.57. Cited to NEC 220.57. The code text itself is not freely available to link; confirm the figure against the current edition or your authority having jurisdiction before acting. Before you commit to a charging schedule, estimate the running cost with our kWh calculator.

Frequently Asked Questions

Glossary

Connected Load

The total wattage of all electrical devices that could potentially run at the same time on a circuit or panel. This is always higher than the actual demand load because not everything runs simultaneously.

Demand Factor

The percentage of a load that a calculation counts. On the optional-method worksheets it applies to the general load: Sacramento's form prints "1st 10,000 watts of SUBTOTAL @ 100%" and the remaining watts "@40%".

Continuous Load

A load the code defines as continuous: one whose maximum current is expected to run for a long time without interruption. NEC requires continuous loads to be sized at 125% of their rated current, which affects breaker and conductor sizing. To size the breaker for a single branch circuit, see what size breaker a load needs.

Noncoincident Loads

Two loads that are unlikely to run at the same time, such as electric heat and air-conditioning. NEC 220.60 lets you count only the larger of the pair in a service calculation and drop the smaller. It is the reason a standard-method dwelling calculation keeps the larger of the heating or cooling load, never the sum of both.

Sizing a solar system to offset your electrical load? Our solar panel and battery sizing calculator designs a complete off-grid system based on your daily usage.

This calculator runs the optional method for one dwelling, line by line as the municipal worksheets print it, and gives the total load, the amperes at 240 V and the next standard overcurrent rating. If you want to size an off-grid system around these loads, start from each load and its hours of use: the total here is a service load, and it does not say how long each load runs. Adding a big new branch, an EV charger above all, can push the total of an existing service toward its rating; our EV charging cost calculator covers the energy side once the panel question is settled. It does not run the standard method's factors per appliance category, or the other heating lines the forms print: the heating input quotes each, with what to enter to follow it. For a permit, your own authority's worksheet governs.

More Electrical calculators

Browse all electrical calculators: Motor FLA, wire sizing, voltage drop, load calculations, and transformer fusing based on NEC standards.

Last updated:

Written and maintained by Dan Dadovic, Commercial Director at Ezoic Inc. & PhD Candidate in Information Sciences. On the energy side, Dan has hands-on experience with residential solar panel installation, DIY battery bank construction, off-grid power systems, wind power, and EV ownership/driving, all from building, maintaining, and operating his own systems.

Disclaimer: Calculator results are estimates based on theoretical formulas. Actual performance varies with temperature, battery age, load patterns, and equipment condition. For critical electrical work, consult a licensed electrician.

Methodology reviewed by Doc. dr. sc. Danijel Jerković-Štil, Assistant Professor, FERIT Osijek.