
How the Battery Count Is Calculated
- Total energy required. Multiply daily usage by autonomy days. For 5,000Wh/day with 2 days of autonomy: 10,000Wh.
- Find the usable watt-hours per amp-hour. Multiply the bank's nominal voltage by the depth of discharge and the inverter efficiency. A 24V LiFePO4 bank is 25.6V nominal, so at 80% DoD and 92% inverter efficiency each amp-hour delivers 25.6 x 0.80 x 0.92 = 18.8416Wh.
- Convert to amp-hours at system voltage. Divide the total energy by that figure. 10,000 / 18.8416 = 530.7Ah at 24V.
- Calculate series batteries per string. Divide system voltage by single battery voltage. For a 24V system using 12V batteries: 24 / 12 = 2 batteries in series per string.
- Calculate parallel strings needed. Divide total Ah by single battery Ah. 530.7 / 100 = 5.31, round up to 6 parallel strings.
- Total battery count. Multiply series count by parallel count. 2 series x 6 parallel = 12 batteries. Each string has 2 batteries in series (for 24V), and you need 6 of these strings in parallel (600Ah at 24V).

Example: Batteries for a Whole-House Solar System
A medium-sized off-grid home using 10,000Wh per day (refrigerator, lighting, well pump, electronics, occasional microwave). The owner wants 3 days of autonomy on a 48V system using 12V 100Ah LiFePO4 batteries at 80% DoD, with a 92% efficient inverter.
Total energy: 10,000 x 3 = 30,000Wh. A 48V LiFePO4 bank is 51.2V nominal, so each amp-hour delivers 51.2 x 0.80 x 0.92 = 37.6832Wh. Convert to Ah at 48V: 30,000 / 37.6832 = 796.1Ah.
Series batteries per string: 48V / 12V = 4 batteries in series. Parallel strings: 796.1 / 100 = 7.96, round up to 8 strings. Total: 4 x 8 = 32 batteries.
A bank that size makes whole-house off-grid systems a major investment, and it is why reducing daily usage (efficient appliances, gas cooking, solar water heating) pays off so directly. Cutting usage from 10kWh to 7kWh runs the same steps to 21,000Wh, 557.3Ah at 48V, and 6 strings of four: 24 batteries. That saves 8 batteries and what they would cost.
Choosing the Right Battery Chemistry
LiFePO4 is this calculator's default chemistry. Battery University's BU-216 table prints an ideal cycle life of 1,000-2,000 cycles for it, and Victron's datasheet prints 2,500 cycles at 80% DoD for its LiFePO4 batteries, in a cycle-life row whose heading includes the words "80 % of nominal". At 80% DoD this calculator sizes fewer batteries than at 50%, as the AGM paragraph below shows. Downside: it cannot charge below 0°C without a heated enclosure.
AGM (Absorbed Glass Mat) is a lead-acid battery. For lead-acid, Trojan recommends a discharge of 20 to 50% and Rolls prints a maximum of 50%. Renogy prints that "Gel and AGM will typically last 500-750 cycles." At the page's defaults (5,000Wh a day, 2 days, a 24V bank of 12V 100Ah batteries, 92% inverter efficiency), this calculator gives 12 batteries for LiFePO4 at 80% DoD and 20 for lead-acid at 50% DoD.
Flooded lead-acid is a third lead-acid type, and the lead-acid figures above apply to it as they do to AGM.
At the DoD figures above LiFePO4 takes fewer batteries for the same daily energy.
Worked Examples
Battery Count for a Remote Communications Relay
Context
Calculation
Total energy = 1,200Wh × 7 days = 8,400Wh
Usable Wh per amp-hour = 12.8V nominal (LiFePO4 at 12V) × 0.80 DoD × 0.92 inverter efficiency (the calculator's default) = 9.4208Wh
Amp-hours at 12V = 8,400 / 9.4208 = 891.6Ah
Series per string = 12V / 12V = 1
Parallel strings = 891.6 / 100 = 8.92 → 9 strings
Total batteries = 1 × 9 = 9 batteries
Interpretation
Nine 100Ah batteries is a serious commitment for a 50W load, but 7 days of autonomy demands it. The system survives a full week of zero sun, critical for mountaintop installations where access during storms is impossible.
Takeaway
High-autonomy systems inflate battery counts fast. Reducing autonomy from 7 to 4 days drops the bank from 9 to 6 batteries. Balance reliability needs against cost, and confirm your panels can recharge the full bank with the solar battery charge time calculator.
Comparing 100Ah vs 200Ah Batteries for a Tiny House
Context
Calculation
Total energy = 4,000 × 2 = 8,000Wh. Usable Wh per amp-hour = 25.6V nominal (LiFePO4 at 24V) × 0.80 DoD × 0.92 inverter efficiency (the calculator's default) = 18.8416Wh
At 24V: 8,000 / 18.8416 = 424.6Ah. Series per string = 24/12 = 2.
With 100Ah batteries: 424.6/100 = 4.25 → 5 parallel strings × 2 series = 10 batteries
With 200Ah batteries: 424.6/200 = 2.12 → 3 parallel strings × 2 series = 6 batteries
Interpretation
The 200Ah option uses 6 batteries vs 10, reducing connection points and simplifying the build. Compare current prices for the exact units before you choose. The FAQ below gives the weights two makers print for their 200Ah units.
Takeaway
Fewer, larger batteries mean a simpler build with fewer connections. Once you've chosen your battery count, verify the bank runs your loads overnight with the deep cycle battery runtime calculator.
Frequently Asked Questions
Glossary
Series String
A set of batteries connected positive-to-negative to increase total voltage while keeping capacity the same. For a 48V system using 12V batteries, each string needs 4 batteries in series. Series wiring is required to match the system voltage.
Parallel Strings
Multiple series strings connected together (positive-to-positive, negative-to-negative) to increase total capacity. Adding parallel strings increases the bank's amp-hour rating without changing voltage.
Nameplate Capacity
The total amp-hour rating printed on a battery, which is larger than usable capacity. A 100Ah battery at 80% DoD provides only 80Ah of usable energy. Battery bank sizing must start from the usable capacity you need divided by DoD, which gives the nameplate capacity to buy.
Battery Management System
An electronic circuit inside LiFePO4 batteries that monitors cell voltages, temperature, and current. The BMS disconnects the battery if any cell reaches dangerous conditions, preventing damage and fire. Quality BMS units also balance cells during charging.
Need to size the solar panels to charge this battery bank? Use our solar panel and battery sizing calculator for the complete picture.
Related calculators
Solar Battery Bank Size Calculator
Calculate the battery bank your off-grid solar system needs. Enter daily usage, autonomy days, chemistry, voltage, depth of discharge and inverter efficiency.
Solar
Solar Panel and Battery Sizing Calculator
Size off-grid solar panels and a battery bank from daily usage, sun hours, losses, chemistry, depth of discharge, autonomy and inverter efficiency.
Solar
How Many Batteries for a Camper?
Calculate how many batteries your camper or van needs from one daily watt-hour total, the days you go without charging and the size of one battery.
Solar
Off-Grid Load Calculator
Calculate your total daily energy needs for off-grid living. Get recommended battery bank size and solar panel wattage for your system.
Solar
Battery count is where solar system costs get real. Every unnecessary battery is money you did not need to spend, and every missing battery is a night without power. Do the math carefully, use honest usage numbers, and pick your chemistry based on lifetime cost, not sticker price. This calculator removes the guesswork so you buy exactly what the system needs. To understand the runtime trade-offs between LiFePO4 and lead-acid, read our LiFePO4 vs lead-acid comparison.
More Solar calculators
Browse all solar calculators: Panel output, battery bank sizing, charge time, and system design for off-grid, RV, and residential setups.
Last updated:
Written and maintained by Dan Dadovic, Commercial Director at Ezoic Inc. & PhD Candidate in Information Sciences. On the energy side, Dan has hands-on experience with residential solar panel installation, DIY battery bank construction, off-grid power systems, wind power, and EV ownership/driving, all from building, maintaining, and operating his own systems.
Disclaimer: Calculator results are estimates based on theoretical formulas. Actual performance varies with temperature, battery age, load patterns, and equipment condition. For critical electrical work, consult a licensed electrician.
Methodology reviewed by Doc. dr. sc. Damir Topić, Assistant Professor, FERIT Osijek.