VoltCalcs

Fusing Transformer Calculator

Enter transformer rating and voltages.

0.1–5000 kVA

100–15000 V

1–15000 V

1–3 x

1–3 x

Primary Fuse

39.1A
Secondary: 208.8A

15 kVA transformer: Primary (480V) = 31.3A FLC, fuse at 39.1A. Secondary (120V) = 125A FLC, fuse at 208.8A.

Source: FLC = kVA / V for single-phase; NEC Article 450.3 Tables for maximum overcurrent protection percentages

5 min read
Size the fuses for any power transformer. Enter the kVA rating, primary and secondary voltages, and the NEC multipliers for your specific installation. The calculator returns the full load current on each side and the recommended fuse sizes.

Why Transformer Fusing Exists

Transformers need overcurrent protection on both sides, but for different reasons. The primary fuse protects the transformer itself from short circuits and overloads on the secondary side. The secondary fuse protects the downstream wiring and loads.

Without proper fusing, a short circuit on the secondary side would cause the transformer to draw excessive current from the primary supply. The transformer's windings overheat, insulation breaks down, and at worst the transformer fails catastrophically — with smoke, fire, or oil rupture on larger units.

The primary fuse also limits the available fault current downstream. A utility service might deliver 10,000+ amps of short circuit current. Without a properly sized primary fuse, that entire fault current flows through the transformer into whatever caused the short.

NEC Article 450 governs transformer protection. The rules differ based on transformer size, impedance, and whether overcurrent protection exists on both sides. Getting this right matters for both safety and code compliance — an inspector will check fuse sizing on any permitted installation.

Step-by-Step Fuse Sizing for Transformers

  1. Calculate the full load current (FLC) on each side. FLC = (kVA x 1000) / Voltage. A 15 kVA transformer at 480V primary draws 31.25A. The same transformer at 120V secondary delivers 125A. The current ratio is the inverse of the voltage ratio — step down the voltage, step up the current.
  2. Apply the primary protection multiplier. NEC 450.3(B) allows the primary fuse to be up to 125% of primary FLC. So 31.25A x 1.25 = 39.06A. Round up to the next standard fuse size: 40A. If 125% does not correspond to a standard fuse size, NEC allows the next size up (up to 150% for primary-only protection).
  3. Apply the secondary protection multiplier. When both primary and secondary protection are provided, NEC allows the secondary fuse up to 125% of secondary FLC. When the secondary is 9A or more, the common practice is 125%: 125A x 1.25 = 156.25A, rounding to a 175A fuse. The 167% multiplier (1.67x) applies in some configurations — check NEC 450.3(B) for your specific case.
  4. Select standard fuse sizes. Fuses come in standard ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600. Your calculated value rounds up to the nearest standard size.
  5. Verify coordination. The primary fuse must clear (blow) before the secondary fuse on a downstream fault. If they do not coordinate, a small secondary fault can trip the primary — taking down everything on that transformer, not just the faulted circuit.

NEC 450.3(B) Protection Multipliers Reference

Protection ConfigurationPrimary (% of FLC)Secondary (% of FLC)NEC Section
Primary only (no secondary protection)125% (next size up to 150%)N/A450.3(B) Column 1
Primary + secondary (secondary ≥ 9A)250%125%450.3(B) Column 2
Primary + secondary (secondary < 9A)250%167%450.3(B) Column 3
Supervised locations300%250%450.3(A)

This calculator defaults to 125% primary and 167% secondary, which is the most common configuration for small to medium dry-type transformers. Adjust the multipliers based on your specific NEC column. The supervised locations rules (NEC 450.3(A)) apply to industrial facilities with qualified personnel — residential and commercial installations use 450.3(B).

For critical electrical installations, always have a licensed electrician verify the fuse sizing against the specific NEC edition adopted by your jurisdiction. Local amendments may modify these values.

Worked Examples

Fusing a 45 kVA Lighting Transformer

Context

A commercial building has a 45 kVA dry-type transformer stepping 480V down to 208V for lighting panels. You need to select primary and secondary fuses per NEC 450.3.

Calculation

Primary FLC: 45,000 / 480 = 93.8 A

Primary fuse (125% per NEC): 93.8 x 1.25 = 117.2 A → next standard size: 125 A

Secondary FLC: 45,000 / 208 = 216.3 A

Secondary fuse (125%): 216.3 x 1.25 = 270.4 A → next standard size: 300 A

Interpretation

The primary side gets a 125A fuse and the secondary a 300A fuse. The secondary fuse is larger in amperage but protects a lower-voltage, higher-current circuit — this is normal.

Takeaway

The loads downstream of this transformer still need individual breakers. Use our amps draw calculator to verify each lighting circuit's current draw before selecting branch breakers.

Protecting a Medium-Voltage Transformer Primary

Context

A 75 kVA transformer has a 4,160V primary (medium voltage) and 480V secondary. NEC allows up to 300% primary fusing for transformers over 1000V per 450.3(A).

Calculation

Primary FLC: 75,000 / 4,160 = 18.0 A

Primary fuse (300%): 18.0 x 3.0 = 54.0 A → use 50 A fuse (next standard size down for MV)

Secondary FLC: 75,000 / 480 = 156.3 A

Secondary fuse (125%): 156.3 x 1.25 = 195.3 A → use 200 A fuse

Interpretation

Medium-voltage primaries use larger multipliers because the low current makes it hard to find fuses that clear faults without nuisance blowing from inrush. The 300% rule gives coordination headroom.

Takeaway

Transformer protection gets complex at higher voltages. For the motors downstream, calculate their individual FLA with our motor FLA calculator to size each motor branch circuit correctly.

Frequently Asked Questions

Glossary

Full Load Current

The current a transformer draws at its rated kVA and voltage. FLC on the primary and secondary sides differ because of the voltage ratio — lower voltage means higher current for the same power.

NEC Fuse Multiplier

NEC Article 450.3 specifies maximum fuse sizes as percentages of the transformer FLC. The multiplier depends on voltage level, transformer type, and whether primary protection alone is used or both primary and secondary.

Inrush Current

The surge of magnetizing current a transformer draws when first energized. Typically 10-15 times the FLC for a fraction of a second. Fuses must be sized large enough to ride through this inrush without blowing.

Planning a battery backup for transformer-fed equipment? Our battery runtime calculator estimates how long your UPS would sustain the load during an outage. Try it now →

Transformer fuse sizing is a code-compliance requirement, not a suggestion. Oversized fuses fail to protect the transformer. Undersized fuses blow under normal load. The values this calculator produces are starting points — verify against the specific NEC edition your jurisdiction enforces and the transformer manufacturer's recommended protection. For any permitted installation, have a licensed electrician specify the final fuse sizes. These results are estimates based on the kVA and voltage values you enter.

Last updated:

Written and maintained by Dan Dadovic, Developer & Off-Grid Energy Enthusiast. On the energy side, Dan has hands-on experience with residential solar panel installation, DIY battery bank construction, off-grid power systems, and wind power — all from building and maintaining his own systems..

Disclaimer: Calculator results are estimates based on theoretical formulas. Actual performance varies with temperature, battery age, load patterns, and equipment condition. For critical electrical work, consult a licensed electrician.