Skip to main content
VoltCalcs

Lead-Acid Battery Runtime Calculator

Calculate lead-acid runtime with proper DoD limits.

1–5000 Ah

1–20000 W

10–80 %

50–100 %

Enter values and click Calculate

Source: Runtime = (Ah x V x DoD x Efficiency) / Load — standard energy-balance discharge calculation

5 min read
Lead-acid batteries remain the most affordable option for stationary storage, backup power, and vehicle starting. But their runtime calculations require more nuance than lithium — the Peukert effect, sulfation risk, and low DoD limits mean the number on the label tells only part of the story. This calculator gives you a baseline estimate with lead-acid-appropriate defaults. If you are sizing a lead-acid bank for solar storage, the solar battery bank calculator factors in the lower DoD limits that lead-acid requires.
Lead-acid battery voltage thresholds from 12.7V charged to 10.5V discharged at 50 percent DoD.

The Peukert Effect in Lead-Acid Batteries

A 100Ah lead-acid battery rated at the 20-hour rate (C20) delivers 5A for 20 hours. Simple math says it should also deliver 50A for 2 hours or 100A for 1 hour. It does not. At 50A, you might get only 1.5 hours (75Ah delivered). At 100A, maybe 40 minutes (67Ah delivered).

The Peukert equation quantifies this: t = C / I^k, where t is time, C is the rated capacity at C20, I is the discharge current, and k is the Peukert exponent. For lead-acid batteries, k ranges from 1.1 (premium AGM) to 1.4 (cheap flooded). Higher k means more capacity loss at high discharge rates.

What causes this? At high currents, lead sulfate crystals form faster than they can dissolve back into the electrolyte. These crystals block the plate surface, preventing further chemical reaction. The energy is not lost — it is trapped in the plates and becomes available when the battery rests or is recharged. But in practice, if you need 100A right now, the Peukert effect means your battery delivers less total energy than the label suggests.

The runtime calculator above uses the simplified linear formula and applies no Peukert correction. For loads below C/5 (20A for a 100Ah battery), it is reasonably accurate. For higher loads, reduce the calculated runtime by 10-25% to account for Peukert losses.

Lead-acid voltage curve showing gradual decline from 12.7V to 10.5V during discharge.
Unlike LiFePO4, lead-acid voltage drops steadily throughout discharge — the 50% DoD cutoff at 11.9V protects longevity.

Flooded Lead-Acid vs Sealed Lead-Acid

FeatureFlooded (FLA)Sealed (SLA/VRLA)
MaintenanceAdd distilled water every 1-3 monthsMaintenance-free
GassingProduces hydrogen when charging — needs ventilationMinimal gassing (recombination)
MountingMust be upright — acid can spillAny orientation (no free liquid)
Cost per AhLowest ($0.40-0.80/Ah)Higher ($1.50-3.00/Ah for AGM)
Cycle Life at 50% DoD600-1,000 cycles400-800 cycles (AGM), 700-1,200 (Gel)
Self-Discharge5-15% per month3-5% per month
Charge AcceptanceModerateGood (AGM can accept higher charge rates)

Flooded batteries win on cost and cycle life but require maintenance and ventilation. Sealed (AGM or Gel) batteries trade cycle life for convenience. For off-grid cabins where you can maintain the batteries, flooded is the value play. For RVs, boats, and enclosed spaces, sealed is safer and more practical.

Worked Examples

Running a 500W Load From a 200Ah Flooded Bank

Context

A 200Ah 12V flooded lead-acid bank runs a 500W inverter load. Flooded lead-acid is held to 50% depth of discharge to protect cycle life, and the inverter and wiring together return about 85% of what leaves the plates.

Calculation

Nameplate energy: 200 x 12 = 2,400 Wh

Usable at 50% DoD: 2,400 x 0.50 = 1,200 Wh

After 85% efficiency: 1,200 x 0.85 = 1,020 Wh

Runtime: 1,020 / 500 = 2.04 hours

Interpretation

Just over two hours, which the calculator above reports as 2 hours 2 minutes. Look at what the nameplate implied: 2,400 Wh reads like nearly five hours at 500W, and the depth-of-discharge limit plus conversion losses remove more than half of it before the load is even connected.

Takeaway

This is the energy-balance figure and it carries no Peukert correction, so treat it as an optimistic ceiling at a draw this heavy. For how depth-of-discharge limits shape long-term cycle life, see our depth of discharge guide.

Sizing a Flooded Lead-Acid Bank for Solar Storage

Context

Your off-grid cabin uses 2,000 Wh per day. You want 2 days of autonomy from a 12V flooded lead-acid bank at 50% DoD with 85% efficiency.

Calculation

Energy needed: 2,000 x 2 = 4,000 Wh

Battery capacity: 4,000 / (12 x 0.50 x 0.85) = 784 Ah

Use 4 x 200Ah batteries in parallel (800Ah)

Interpretation

800Ah at 12V is a large bank — weighing about 240 lbs for flooded batteries. The same energy from LiFePO4 at 80% DoD needs only 490Ah and weighs half as much.

Takeaway

For the solar panel sizing to recharge this bank, use our solar panel and battery sizing calculator — it handles the complete sizing calculation.

Frequently Asked Questions

Glossary

Peukert Effect

The phenomenon where lead-acid batteries deliver less total energy at higher discharge rates. A battery rated 200Ah at the 20-hour rate (10A) might only deliver 140Ah at a 40A rate. The Peukert exponent (typically 1.1-1.3) quantifies this loss.

Flooded Lead-Acid

A battery with liquid sulfuric acid electrolyte that must be periodically topped up with distilled water. Cheapest per Ah but requires maintenance, proper ventilation (hydrogen gas release), and upright mounting.

20-Hour Rate

The standard discharge rate used to define a battery's Ah capacity. A 200Ah battery at the 20-hour rate delivers 10A for 20 hours. Drawing more than 10A reduces the effective capacity due to the Peukert effect.

Planning solar charging for your lead-acid bank? The solar charge time calculator accounts for the slow absorption phase that lead-acid requires.

Lead-acid batteries are proven, affordable, and widely available. They are also heavy, maintenance-intensive, and limited to 50% usable capacity. Run the numbers above with 50% DoD and 85% efficiency — those are the honest defaults for lead-acid. If the runtime falls short, you need a bigger bank or a different chemistry. For a head-to-head comparison with lithium, read our LiFePO4 vs lead-acid runtime comparison. The deep cycle runtime calculator covers flooded, gel, and golf-cart batteries with Peukert-effect guidance.

More Battery calculators

Browse all battery calculators — LiFePO4, lead-acid, AGM, and lithium-ion runtime, charge time, and capacity sizing.

Last updated:

Written and maintained by Dan Dadovic, Commercial Director at Ezoic Inc. & PhD Candidate in Information Sciences. He works professionally as Commercial Director at Ezoic Inc., leading revenue strategy across digital publishing.

Disclaimer: Calculator results are estimates based on theoretical formulas. Actual performance varies with temperature, battery age, load patterns, and equipment condition. For critical electrical work, consult a licensed electrician.

Methodology reviewed by Doc. dr. sc. Damir Topić, Assistant Professor, FERIT Osijek.